Global Building and Design Directory is part of the Informa Markets Division of Informa PLC

This site is operated by a business or businesses owned by Informa PLC and all copyright resides with them. Informa PLC's registered office is 5 Howick Place, London SW1P 1WG. Registered in England and Wales. Number 8860726.

Cooling Towers — Paragon Induced Draft Towers

Paragon Induced Draft Towers

Delta's Paragon® Induced Draft, counter flow cooling tower design is available in single module capacities from 55 to 250 cooling tons.

Standard Features

  • Seamless Engineered Plastic (HDPE) Shell
  • Corrosion Proof Construction
  • Direct Drive Fan System
  • Totally Enclosed VFD Rated Motors
  • Factory Assembled for Simple Installation
  • 20 Year Shell Warranty
  • Low Pressure Drop Self Propelled PVC Water Distribution System
  • High Efficiency PVC Fill
  • Made in the USA

Detailed Features

All Delta Cooling Towers are factory assembled to the fullest extent possible for ease of installation and shipment. The following features are standard on our Paragon® Series Induced Draft Cooling Towers:

Shell: A seamless engineered polyethylene cylindrical (HDPE) molded shell, with conical transition for motor/fan assembly, louvered inlets and fitting orientation. Louvered inlets are designed for 360° air distribution. There are no joints, seams, panels, gaskets, bolts, fasteners or caulking like conventional towers.

Sump: Sump is integral with cooling tower shell, creating a one-piece seamless structure.

Water Distribution System: A self propelled PVC distribution system incorporating a rotating sprinkler head and lateral distribution arms with integral drift eliminators. An inspection port is provided in the cooling tower shell at the lateral arm elevation for adjustment. (Non-rotating water distribution system is also available).

Wet Decking: A continuous wrapped spiral configuration of lightweight PVC, bonded and packed for maximum film cooling efficiency.

Fan Assembly: The fan assembly consists of a fan ring, propeller, motor and guard. The fan ring is coated with premium plasite coating ideal for the harshest corrosive environments. An adjustable pitch propeller fan, fiberglass reinforced polypropylene with a silica alloy hub, is directly driven by a totally enclosed VFD Premium rated motor designed for cooling tower duty. A fan guard is included that allows protection from the propeller and access to the motor.

Motor: Totally enclosed air over (TEAO) VFD rated motor with 1.15 service factor, designed for 208 or 230/460V 3 phase 60 cycle operation and suitable for outdoor service. Motor is provided with a 5-year motor manufacturers warranty.

Fitting Connections: PVC fittings are provided for inlet, outlet, overflow, drain

Hardware: All fasteners are 304 stainless steel. Anchor and lifting lugs are aluminum.

View this product at deltacooling.com